Navigate to [https://192.168.1.50/hsycoserver/manager.login](https://192.168.1.50/hsycoserver/manager.login) and login
2
Enter "Settings" menu.
3
Click "I/O SERVERS".
4
Click "+"
5
Click the input field "Comm ID".
6
Select the correct communication port. The serial RS485 port on every HSYCO Strato based server is already declared and set to: Port=ttyAMAO, Baud Rate=57600, Data Bits=8, Stop Bits=1, Parity=none, Flow Control=none
7
Click "+" to add server options.
8
Click this input field to select an option.
9
Select "controllerrangelist" to specify the ids of all the room unit controllers installed. You can use "-" to specify a range and "," for multiple ranges, for example: 1-3,9-10 means the room controllers with ids: 1,2,3,9,10
10
Click the input field "value" to set the option parameters.
11
Type "1-2;6-7" to set the values for "controllerrangelist" option.
12
Click "OK"
13
Repeat the steps from 7 to 12 for each new option to add. The options: gui, startupevents, debug, and pollingtime could be left blank. The option: controllersmaxaddress it's an alternative to controllerrangelist. For example controllersmaxaddress=30 means from controller id 1 to 30