Configure Rosslare 825-IP Controller (6 door, 1 - Reader Per Door Configuration)
Aaron Newman
47 steps
5 minutes
Qumulex
1
Navigate to <https://app.qumulex.io/qx/gateways> \ \ **Before You Begin**\ Before starting the commissioning process for the Rosslare 825, ensure that all required **Schedules** and **Places** have been created. These will be needed in later steps of the setup process.
2
Go to **Gateways** from the left navigation panel.
3
Select the **Gateway** that the Rosslare 825 will be associated with.
4
Click the **Actions** button.
5
From the **Actions** dropdown, click **Rosslare Scan**.\ \ **Troubleshooting** - If the controller is not discovered: - Verify the controller’s MAC address is visible in an **ARP search**. - Connect the panel locally to the gateway if the IP address needs to be changed before deployment on a managed network. - Qumulex automatically scans both NICs using broadcast messaging to locate Rosslare devices.
6
After the scan completes, the **Rosslare 825 Controller** will appear in the results.\ \ **Important Notes** - Qumulex supports **AxTrax Pro Firmware version AC825V05_00_03 or newer**. - If the **Version** field is blank, the controller is running an unsupported firmware version and is **not compatible with Qumulex**. The controller must be upgraded first.
7
Tick the checkbox for the controller, then click **Select Devices**.
8
When prompted that the controller requires additional configuration, click **Needs Config**.
9
Click the **Name** text field and enter a unique, descriptive name for the controller.\ \ **Recommendation:** Use a name that is meaningful to both the installer and the customer, such as the **location** or another clear identifier.
10
In this guide, the controller is named **“Rosslare 825-IP”** since it is the only controller on this gateway.
11
To change the controller’s IP address, enter the new value in the **Hostname / IP Address** field within the **Configuring Devices** dialog.
12
Click **OK**.
13
Click **Add Devices**.
14
Click **Devices**.
15
Click the newly commissioned **825 Controller**.
16
Click **Edit Device**.
17
From the **Device Protocol** dropdown, select **Standard**. - Reader Ports 1–4 are configured for **Wiegand**. - Doors 5–6 are configured for **OSDP**. **Options:** - From the same dropdown, you can also select **OSDP** for all six doors if required. **Notes (Rosslare Defaults):** - **Door 5:** OSDP address **13** - **Door 6:** OSDP address **14** - **Baud Rate:** 9600 (default)
18
Select the **1 Reader Per Door** option.
19
Click **Save Device**.
20
After saving the configuration, click **Edit Device** again to open the **Door Editor**.
21
Click **Rosslare Door 1**.
22
Open the **Unlock Schedule** dropdown. **Recommendation:** Set the schedule to **Never** if the door should remain secure 24/7, allowing access **only with valid credentials**.
23
From the **Unlock Schedule** dropdown, select **Never (Read only)**.
24
Click **Select a Place**. The area on the **unsecured side** of the door is defined (in a single-reader configuration).
25
In this guide, **Public Space** is selected as the **From Place**, representing the unsecured side of the door.
26
Open the **To Place** dropdown. This defines the area on the **secure side** of the door. The selected **To Place** will be tied to permissions and ultimately included in an **Access Group**.
27
In this guide, **Door 1** is selected as the **To Place**, representing the secure side of the door that will be tied to permissions and access groups.
28
Select the **Door Contact** setting. **Options:** - **None** – No door contact is configured. - **Normally Closed** – Contact is closed when the door is secure. - **Normally Open** – Contact is open when the door is secure. **Example:** In this guide, **Normally Open – Door Contact** is selected.
29
Define the **Reader Settings** by selecting the place the reader will be associated with.\ \ Choose the **secure side** of the door.\ \ **Example:** In this guide, click **Regional Office – NYC**.
30
From the **Card Format** dropdown, select **26-bit (H10301)**. The reader is configured to support the most common format for low-frequency cards. **Notes:** - If the site uses additional card types, you can add them from the **Secondary Card Format** menu.
31
Configure the **REX (Request to Exit)** place settings.\ Select the **Non-Secure** side of the door. The REX will grant access from the secure area to the **Non-Secure** side when activated.
32
Define the **Input Settings** for the door.\ \ Select **Normally Open**.\ \ The controller will treat the input as active when the circuit is closed, based on the selected configuration.
33
Configure the **Lock Settings**.\ \ Click **Relay**.\ \ The door lock will be controlled through the assigned relay output.
34
Set the **Relay Settings** for the lock.\ \ **Example:** Select **Relay Open = Unlocked** to configure the lock as a **Normally Closed** circuit.\ \ When the relay is energized, the circuit opens and the door unlocks.
35
Click **Next** to proceed to **Door 2**. The configuration page for Door 2 opens.
36
Repeat the same configuration process for **Doors 2–6**.\ \ All doors on the Rosslare 825 are configured with the appropriate reader, schedule, input, and lock settings.
37
**Optional Step:** If you only need to configure a few doors, remove any unused doors from the setup.\ \ Click the **trash can icon** in the upper-right corner of the door card.\ \ The selected door is removed from the configuration.
38
Click **Delete Door** to confirm removal.
39
Click **I understand, Delete Door** to confirm the deletion.
40
Repeat this process as many times as needed for additional doors.\ \ All required doors are removed from the configuration.
41
Click **Save Device** when you are ready to commit the configuration.\ \ All changes are saved, and the Rosslare 825 controller is now fully commissioned with the selected door, reader, and lock settings.
42
From the **825 Device Page**, open the **Config** menu.\ The configuration options for pushing settings to the controller are displayed.
43
Push Configuration to Controller. Click **Update** within the **Config** menu on the 825 Device Page.\ \ he **Panel State** indicator (upper right-hand corner) shows progress, turning green when the panel is fully configured.
44
Click **Doors**.
45
From the **Doors** page, locate the newly created doors. These doors are now also available within the **Rules Engine**.
46
Click **Unlock** on the selected door.\ \ The panel triggers the lock relay, and the door should unlock, confirming proper lock operation.
47
Monitor **Recent Events** for the door.\ \ You can verify that: - **Card reads** are being logged and match the configured **card format settings**. - **Door operations** (unlocks/locks) are recorded successfully.
Configure Rosslare 825-IP Controller (6 door, 1 - Reader Per Door Configuration)
Aaron Newman
47 steps
5 minutes
Qumulex
1
Navigate to <https://app.qumulex.io/qx/gateways> \ \ **Before You Begin**\ Before starting the commissioning process for the Rosslare 825, ensure that all required **Schedules** and **Places** have been created. These will be needed in later steps of the setup process.
2
Go to **Gateways** from the left navigation panel.
3
Select the **Gateway** that the Rosslare 825 will be associated with.
4
Click the **Actions** button.
5
From the **Actions** dropdown, click **Rosslare Scan**.\ \ **Troubleshooting** - If the controller is not discovered: - Verify the controller’s MAC address is visible in an **ARP search**. - Connect the panel locally to the gateway if the IP address needs to be changed before deployment on a managed network. - Qumulex automatically scans both NICs using broadcast messaging to locate Rosslare devices.
6
After the scan completes, the **Rosslare 825 Controller** will appear in the results.\ \ **Important Notes** - Qumulex supports **AxTrax Pro Firmware version AC825V05_00_03 or newer**. - If the **Version** field is blank, the controller is running an unsupported firmware version and is **not compatible with Qumulex**. The controller must be upgraded first.
7
Tick the checkbox for the controller, then click **Select Devices**.
8
When prompted that the controller requires additional configuration, click **Needs Config**.
9
Click the **Name** text field and enter a unique, descriptive name for the controller.\ \ **Recommendation:** Use a name that is meaningful to both the installer and the customer, such as the **location** or another clear identifier.
10
In this guide, the controller is named **“Rosslare 825-IP”** since it is the only controller on this gateway.
11
To change the controller’s IP address, enter the new value in the **Hostname / IP Address** field within the **Configuring Devices** dialog.
12
Click **OK**.
13
Click **Add Devices**.
14
Click **Devices**.
15
Click the newly commissioned **825 Controller**.
16
Click **Edit Device**.
17
From the **Device Protocol** dropdown, select **Standard**. - Reader Ports 1–4 are configured for **Wiegand**. - Doors 5–6 are configured for **OSDP**. **Options:** - From the same dropdown, you can also select **OSDP** for all six doors if required. **Notes (Rosslare Defaults):** - **Door 5:** OSDP address **13** - **Door 6:** OSDP address **14** - **Baud Rate:** 9600 (default)
18
Select the **1 Reader Per Door** option.
19
Click **Save Device**.
20
After saving the configuration, click **Edit Device** again to open the **Door Editor**.
21
Click **Rosslare Door 1**.
22
Open the **Unlock Schedule** dropdown. **Recommendation:** Set the schedule to **Never** if the door should remain secure 24/7, allowing access **only with valid credentials**.
23
From the **Unlock Schedule** dropdown, select **Never (Read only)**.
24
Click **Select a Place**. The area on the **unsecured side** of the door is defined (in a single-reader configuration).
25
In this guide, **Public Space** is selected as the **From Place**, representing the unsecured side of the door.
26
Open the **To Place** dropdown. This defines the area on the **secure side** of the door. The selected **To Place** will be tied to permissions and ultimately included in an **Access Group**.
27
In this guide, **Door 1** is selected as the **To Place**, representing the secure side of the door that will be tied to permissions and access groups.
28
Select the **Door Contact** setting. **Options:** - **None** – No door contact is configured. - **Normally Closed** – Contact is closed when the door is secure. - **Normally Open** – Contact is open when the door is secure. **Example:** In this guide, **Normally Open – Door Contact** is selected.
29
Define the **Reader Settings** by selecting the place the reader will be associated with.\ \ Choose the **secure side** of the door.\ \ **Example:** In this guide, click **Regional Office – NYC**.
30
From the **Card Format** dropdown, select **26-bit (H10301)**. The reader is configured to support the most common format for low-frequency cards. **Notes:** - If the site uses additional card types, you can add them from the **Secondary Card Format** menu.
31
Configure the **REX (Request to Exit)** place settings.\ Select the **Non-Secure** side of the door. The REX will grant access from the secure area to the **Non-Secure** side when activated.
32
Define the **Input Settings** for the door.\ \ Select **Normally Open**.\ \ The controller will treat the input as active when the circuit is closed, based on the selected configuration.
33
Configure the **Lock Settings**.\ \ Click **Relay**.\ \ The door lock will be controlled through the assigned relay output.
34
Set the **Relay Settings** for the lock.\ \ **Example:** Select **Relay Open = Unlocked** to configure the lock as a **Normally Closed** circuit.\ \ When the relay is energized, the circuit opens and the door unlocks.
35
Click **Next** to proceed to **Door 2**. The configuration page for Door 2 opens.
36
Repeat the same configuration process for **Doors 2–6**.\ \ All doors on the Rosslare 825 are configured with the appropriate reader, schedule, input, and lock settings.
37
**Optional Step:** If you only need to configure a few doors, remove any unused doors from the setup.\ \ Click the **trash can icon** in the upper-right corner of the door card.\ \ The selected door is removed from the configuration.
38
Click **Delete Door** to confirm removal.
39
Click **I understand, Delete Door** to confirm the deletion.
40
Repeat this process as many times as needed for additional doors.\ \ All required doors are removed from the configuration.
41
Click **Save Device** when you are ready to commit the configuration.\ \ All changes are saved, and the Rosslare 825 controller is now fully commissioned with the selected door, reader, and lock settings.
42
From the **825 Device Page**, open the **Config** menu.\ The configuration options for pushing settings to the controller are displayed.
43
Push Configuration to Controller. Click **Update** within the **Config** menu on the 825 Device Page.\ \ he **Panel State** indicator (upper right-hand corner) shows progress, turning green when the panel is fully configured.
44
Click **Doors**.
45
From the **Doors** page, locate the newly created doors. These doors are now also available within the **Rules Engine**.
46
Click **Unlock** on the selected door.\ \ The panel triggers the lock relay, and the door should unlock, confirming proper lock operation.
47
Monitor **Recent Events** for the door.\ \ You can verify that: - **Card reads** are being logged and match the configured **card format settings**. - **Door operations** (unlocks/locks) are recorded successfully.